13

031-103-B0-004, Rev. D

E nc los ure F ootprint

20 feet (minimum)

2

fe

et

(m

in)

30

in

ches

Side View

UFER Ground

SE

conduit &

wires

GEC

#2 bare
copper

wire

No

separation

is required

#2 AWG

#2 AWG

Opening

for

Sweeps

Opening

for

Sweeps

Opening

for

Sweeps

Connection Made With

Burndy Connector

P/N YGHP58C2W-2TN

Or Equivalent

Connection Made With

Burndy Connector

P/N YGHR58C2W-3

Or Equivalent

Lightning Protection (Optional)

1

1/2" x 8' copper ground rod, four places, driven about 2 feet (typical) from the corners of the pad.

2

#2 bare copper wire loop terminated to each ground rod and buried below grade 2 to 12 inches.
Corrosion-proof connections (25+ year life-span) and hardware suitable for direct burial MUST be
used.

3

#2 bare copper wire from loop to the enclosure.

4

When the electrical supply is a primary service (not a secondary or feeder service) a #2 bare copper
wire must be bonded to the lightning protection loop to the Grounding Electrode Conductor where
they are closest.

Service Grounding (required)

5

#2 bare copper wire from Service Neutral/Ground Bar down 30" and out 20' beyond the pad edge.
This is often called a UFER ground (Ground Ring in the NEC).

1

2

3

4

5

Fig. 3-4, Alternate Grounding, PN-3 and PN-4

3.0

Site Preparation, continued

3.2

Enclosure Grounding, continued