4 pneumatic connection 8.5 removal – Burkert Type 2012 User Manual

Page 18

Advertising
background image

18

Installation

Type 2012

8.4

pneumatic connection

Danger!

danger – high pressure in the equipment!

▶ Before loosening the lines and valves, turn off the pressure and

vent the lines.

Warning!

risk of injury from unsuitable connection hoses!
Hoses which cannot withstand the pressure and temperature range
may result in hazardous situations.

▶ Use only hoses which are authorised for the indicated pressure

and temperature range.

▶ Observe the data sheet specifications from the hose manufacturers.
for control function i – danger if pilot pressure fails!
For control function I control and resetting occur pneumatically. If
the pressure fails, no defined position is reached.

▶ To ensure a controlled restart, first pressurize the device with pilot

pressure, then switch on the medium.

If the position of the pilot air ports for installation of the hoses
is unfavorable, these can be aligned steplessly by rotating
the actuator through 360°.

control function a

Connect the control medium to the lower control air connection
of the actuator.

control function B

Connect the control medium to the upper control air connection
of the actuator.

control function i

Connect the control medium to the lower and upper control air
connection of the actuator.

If used in an aggressive environment, we recommend con-
veying all free pneumatic connections into a neutral atmo-
sphere with the aid of a pneumatic hose.

control air hose:
6/4 mm or 1/4” control air hoses can be used.

8.5

removal

Danger!

risk of injury from discharge of medium and pressure!
It is dangerous to remove a device which is under pressure due to
the sudden release of pressure or discharge of medium.

▶ Before removing a device, switch off the pressure and vent the

lines.

procedure:

Loosen the pneumatic connection.

Remove the device.

english