9 maintenance, cleaning, 1 safety instructions 9.2 maintenance work, 9maintenance, cleaning – Burkert Type 2012 User Manual

Page 19

Advertising
background image

19

Maintenance,Cleaning

Type 2012

9

mainTenance, cleaning

9.1

safety instructions

Danger!

danger – high pressure in the equipment!

▶ Before loosening the lines and valves, turn off the pressure and

vent the lines.

risk of injury due to electrical shock!

▶ Before reaching into the system, switch off the power supply and

secure to prevent reactivation!

▶ Observe applicable accident prevention and safety regulations

for electrical equipment!

Warning!

risk of injury from improper maintenance!

▶ Maintenance may be performed by authorised technicians only!

▶ To screw on or unscrew valve body or actuator, use an open-end

wrench, never a pipe wrench, and observe tightening torques.

risk of injury from unintentional activation of the system and
an uncontrolled restart!

▶ Secure system from unintentional activation.

▶ Following maintenance, ensure a controlled restart.

Warning!

for control function i – danger if pilot pressure fails!
For control function I control and resetting occur pneumatically.
If the pressure fails, no defined position is reached.

▶ To ensure a controlled restart, first pressurize the device with pilot

pressure, then switch on the medium.

risk of injury from moving parts in the device!

▶ Do not reach into openings.

9.2

maintenance work

actuator:
The actuator of the globe control valve is maintenance-free provided
it is used according to these operating instructions.

Wearing parts of the globe control valve:
Parts which are subject to natural wear:
• Valve seat,
• Seals.

If leaks occur, replace the particular wearing part with an appro-
priate spare part.

Visual inspection:
Perform regular visual inspections according to the application
conditions:

Check media connections for leaks.

Check release bore on the tube for leaks.

english