Electrical data – Burkert Type 3004 User Manual

Page 18

Advertising
background image

18

Technical Data

6.6.3.

Electrical data

Connections:

2 threaded connections ISO 20

Limit switches:

2 limit switches for the motor

2 potential-free limit switches (for position feedback)

Output:

max. 250 V AC / 5 A

Electrical data for standard version without analogue signal and position controller version with 4 – 20 mA,
0 – 20 mA or 0 – 10 V analogue input signal

Torque [Nm]

90° actuating time [s]

Power input [W]

Voltage / frequency

[V / Hz]

25

7

45

100-240 / 50/60 (100-350 DC)
15-30 AC (12-48 DC

1)

)

45

15

45

100-240 / 50/60 (100-350 DC)
15-30 AC (12-48 DC

1)

)

75

20

45

100-240 / 50/60 (100-350 DC)
15-30 AC (12-48 DC

1)

)

100

15

45

100-240 / 50/60 (100-350 DC)
15-30 AC (12-48 DC

1)

)

150

30

45

100-240 / 50/60 (100-350 DC)
15-30 AC (12-48 DC

1)

)

300

60

45

100-240 / 50/60 (100-350 DC)
15-30 AC (12-48 DC

1)

)

We recommend an actuator designed with 1.5 times the maximum torque of the fitting (with 2 times
the maximum torque for variable speed actuators)

1)

The operating voltage must not drop below 11.5 V