Installation

Learning mode

Specify end positions

G

R

Press <OPEN> and <CLOSE> push-buttons and switch on the card
(hold down push-button).

The RED and the GREEN LEDs light up.

Release <OPEN> and <CLOSE> push-buttons.

Both LEDs go out.

Learning mode is selected.

R

Press <CLOSE> push-button to move the shut-off valve into the
closed position.

The RED LED lights up.

R

Press <MEM> and <CLOSE> push-buttons to save the closed
position.

The RED LED lights up 2x.

G

Press <OPEN> push-button to move the shut-off valve into the open
position.

The GREEN LED lights up.

G

Press <MEM> and <OPEN> push-buttons to save the open position.

The GREEN LED lights up 2x.

All positions are now saved.

Disconnect the card from the power supply.

8.3.3.

Normal operation

Display normal operation

G

Switch on card.

The GREEN LED lights up 3x to indicate that the start process has been
implemented correctly.

G

In normal operation the GREEN LED lights up when the rotary actuator
opens the shut-off valve.

R

The RED LED lights up when the rotary actuator closes the shut-off valve.

G

R

If neither of the LEDs is lit, the actuator is not actuated.

G

R

The RED and the GREEN LEDs light up if the torque is too high and the
rotary actuator stops.

Change direction of rotation of the rotary actuator or switch over the
voltage OPEN/CLOSED to restart the rotary actuator!