Burkert Type 3004 User Manual

Page 25

Advertising
background image

25

Installation

Auf

Zu

N

-

Ph

+

1

2

3

T/E

Auf

N

-

Ph

+

3

2

1

T/E

Figure 16:

Three points mode

Figure 17:

Open / Closed mode / Emergency current
model

If voltage is applied simultaneously to terminals 2 and 3, terminal 2 is the leading one and the actuator
moves to the OPEN position.

Procedure:

Loosen left cable gland 15 (see “Figure 1” and “Figure 2”) and feed through the cable to be connected.

Connect cable according to the required control type (see “Figure 16” and “Figure 17”) to the terminal strip Pos.
B of the power supply card (see “Figure 14” and “Figure 15”).

Operating principle for Open / Closed mode (see “Figure 17”) :
• Switch open = actuator closes

• Switch closed = actuator opens

Connecting feedback

The limit switches for the feedback are suitable for a maximum voltage of 250 V AC/DC – 5 A.

The rotary actuator features two additional limit switch contacts which are supplied by the factory in an open position.
These can be used for the feedback of the rotary actuator.

2

3

1

FC2

FC1

FCF

FC0

4-6

5

7

=

C

C

A

B

D

D

T/E

Motor

Feedback

Power supply and control

Figure 18:

Internal wiring of actuator

English

Type 3004