26

Installation

The limit switch contacts are actuated via two cams no. 13
(see “Figure 1”, page 10 and “Figure 2”, page 11).

• The white cam is used to record the opening process (FC1).

• The black cam is used to record the closing process (FC2).

Procedure:

Connect cable to the terminal strip 12 (see “Figure 1”, page 10 and “Figure 2”, page 11) according to the
schematic (see “Figure 18”).

8.2.3.

Version with analog signal input

The power supply voltage of the actuator is 15-30 V AC (12-48 V DC) or 100-240 V AC
(100-350 V DC).

Always observe the specifications on the rating plate!

0 – 20 mA / 4 – 20 mA / 0 – 10 V

T/E

FC2

FC1

FCF

FC0

4-6

5

7

=

C

B

D

D

A

C

2

17

18

18

17

N

-

Ph

+

N

-

Ph

+

3

1

16

15

14

13

+

-

-

+

Motor

Feedback

Power supply

100-240 V AC
(100-350 V DC)
or
15-30 V AC
(12-48 V DC))

Input

Feedback

Power supply

24 V DC

Figure 19:

Circuit diagram

Procedure:

Loosen left cable gland 15 and feed through the cable to be connected (see “Figure 1”, page 10 and “Figure
2”, page 11).

Connect cable according to the circuit diagram (see “Figure 19”) to the terminal strip Pos. 14 of the power supply card
(see “Figure 1”, page 10 and “Figure 2”, page 11).

English

Type 3004