Power connection, Power connection -7, Figure 3-5. four-point terminal block -7 – ADTRAN Total Access 1240 User Manual

Page 29

Advertising
background image

Section 3, Installation - Ground and Power Connections

61179605L5-5B

3-7

Power Connection

The Total Access 1240 uses a four-point terminal block (see

Figure 3-5

) to accept the

–48 VDC and –48 VDC RET leads.

Figure 3-5. Four-point Terminal Block

NOTE

If a non-redundant power configuration is to be implemented, use
the connections marked

–48 VDC A

and

–48 VDC A RET

.

To connect the power source, perform the following steps:

1. With the power disconnected at the source, remove approximately 1/4-inch of insulation

from the ends of both power wires.

NOTE

ADTRAN recommends an external fuse rated between 1.5 to 2.0
amps.

2. Using a small flat-head screwdriver, loosen the setscrews on the top of the terminal block.
3. Insert the bare wire into the opening on the front of the terminal block.
4. While holding the wire in place, tighten the setscrew until the wire is secure.
5. Repeat this procedure until all power leads are connected, making sure that the wires are

connected using correct polarity according to the labeling on the unit above the terminal
block.

6. Apply power to the Total Access 1240 and test the voltage and polarity on the terminal

block using the tops of the setscrews as test points.

-48 VDC B RET

-48 VDC A RET

-48 VDC A

-48 VDC B