Inputs - outputs, Applications – Micromod RetroPAK: SLC Configuration Manual User Manual
Page 288
Advertising

Command Series Migration to MOD 30ML
Function Code 51- Manual Set Constant
INPUTS - OUTPUTS
Signal
Type
Block
Description
S1
Input – S1
Floating Point
FC2 (EX
block)
Initial value of the input is typed in the
input configuration. The value of the input
can be changed from instrument display if
configured.
N Output
-
Floating Point
FC2
Connect from the R (result) attribute of
the EX block. This is the manual set
constant value.
To change the value of S1 and its data type, open the EX block and then click on the
Inputs tab. See the figure below:
APPLICATIONS
This compound is meant for storing of values that be used in applications such as Setpoint,
signal scaling or Biasing, and wherever you need a constant value.
51 - 2