Command Series Migration to MOD 30ML
Function Code 156 – Auto Bias Station
MULTIPLIER INPUT.
S12
AUTO BIAS
Input – GAIN
Floating Point
Proportional Gain Kp. Enter in the
AUTO BIAS block. Open the General
tab and type a value in the BASE GAIN
– BASE VALUE filed.
S13
AUTO BIAS
Input – RESET
Floating Point
Integral Reset in resets/min (RPM) Ki.
Enter in the AUTO BIAS block. Open
the General tab and type a value in the
BASE RESET RATE – BASE
VALUE filed.
S14
AUTO BIAS
Input – PREACT
Floating Point
Derivative rate in minutes Kd. Enter in
the PID block. Open the General tab
and type a value in the BASE PREACT
TIME – BASE VALUE filed.
S15
AUTO BIAS
Input – Floating
Point
Derivative Lag constant Ka. Enter the
value in the AUTO BIAS block. Open
the Control tab and change the INPUT
FILTER TPE to PRE-ACT USER and
type the value in the INPUT FILTER
TIME field.
S16
AUTO BIAS
Input – Floating
Point
High Output Limit. Enter the value in
the AUTO BIAS block. Open the
Output tab and change the OUTPUT
LIMITS HIGH field and OUTPUT
RANGE HIGH field.
S17
AUTO BIAS
Input – Floating
Point
Low Output Limit. Enter the value in
the AUTO BIAS block. Open the
Output tab and change the OUTPUT
LIMITS LOW field and OUTPUT
RANGE LOW field.
S18 N/A
N/A
N/A
S19 N/A
N/A
N/A
S21
AUTO BIAS
Input – Discreet
Controller Action. Choose the action in
the PID (AUTO BIAS) block. Open the
General tab and select the desired
CONTROLLER ACTION.
N
AUTO BIAS
Output – N
Floating Point
Output of the compound. Connect from
the AUTO BIAS.N signal of the
compound.
156ab - 3