Micromod RetroPAK: SLC Configuration Manual User Manual

Page 377

Advertising
background image

Command Series Migration to MOD 30ML

Function Code 156 – Auto Bias Station


MULTIPLIER INPUT.

S12

AUTO BIAS

Input – GAIN
Floating Point

Proportional Gain Kp. Enter in the
AUTO BIAS block. Open the General
tab and type a value in the BASE GAIN
– BASE VALUE
filed.

S13

AUTO BIAS

Input – RESET
Floating Point

Integral Reset in resets/min (RPM) Ki.
Enter in the AUTO BIAS block. Open
the General tab and type a value in the
BASE RESET RATE – BASE
VALUE
filed.

S14

AUTO BIAS

Input – PREACT
Floating Point

Derivative rate in minutes Kd. Enter in
the PID block. Open the General tab
and type a value in the BASE PREACT
TIME – BASE VALUE
filed.

S15

AUTO BIAS

Input – Floating
Point

Derivative Lag constant Ka. Enter the
value in the AUTO BIAS block. Open
the Control tab and change the INPUT
FILTER TPE
to PRE-ACT USER and
type the value in the INPUT FILTER
TIME
field.

S16

AUTO BIAS

Input – Floating
Point

High Output Limit. Enter the value in
the AUTO BIAS block. Open the
Output tab and change the OUTPUT
LIMITS HIGH
field and OUTPUT
RANGE HIGH
field.

S17

AUTO BIAS

Input – Floating
Point

Low Output Limit. Enter the value in
the AUTO BIAS block. Open the
Output tab and change the OUTPUT
LIMITS LOW
field and OUTPUT
RANGE LOW
field.

S18 N/A

N/A

N/A

S19 N/A

N/A

N/A

S21

AUTO BIAS

Input – Discreet

Controller Action. Choose the action in
the PID (AUTO BIAS) block. Open the
General tab and select the desired
CONTROLLER ACTION.

N

AUTO BIAS

Output – N
Floating Point

Output of the compound. Connect from
the AUTO BIAS.N signal of the
compound.

156ab - 3