Fulton Thermal Corp.*SteamPac Unfired Steam Generators Manual* Version 2010-0201

Page 15

d) Make sure two check valves are installed between the SteamPac and feedwater pump.

e) An end of the line trap should be installed in the SteamPac steam header.

f) There are three valves on the SteamPac: the main blowdown valve, the gauge glass

drain valve, and the water column drain valve. The SteamPac blow off valve supplied

with the SteamPac should be installed on the blow off pipe and connected to a blow off

receptacle of approved design.

g) With a pressure transducer, this control sends out a 4 – 20 ma signal to modulate the

thermal fluid valve. The controller also sends out a 120V signal to energize an air

solenoid on the modulating valve. In the event the steam pressure exceeds the set point

by (X) PSI, the valve will de-energize sending the modulating valve to its fail position.

h) All these procedures should be done in accordance with state and/or local codes. The

water column blow off valve and the gauge glass blow off valve should be connected to

the main blow off line.

Caution

Do not tamper with the safety features of the low water safety cut out.

i)

Pressure Relief Valve

1. Limits maximum operating pressure of the SteamPac.

j)

Operating Seam Pressure Control

1. Located at the control panel box is a digital process control. The

pressure control regulates the thermal fluid control valve, diverting the

flow of fluid when maximum pressure is reached and opening the valve

when the steam pressure falls below a predetermined level.

k) Sight Glass Isolation Valves

1. The brass sight glass isolation valves are equipped with an internal ball

check. In the event that a sight glass should break, the ball will seat,

preventing the discharge of steam and water. The brass valve stem must

be opened fully to enable this feature. If the valve is in any other position

than full open, the ball will not seat. For added safety all Fulton boilers

are equipped with gauge glass protectors.

l)

High Limit Pressure Control

1. Located at the control panel box and connected to the steam pressure

gauge assembly by means of a copper tube. The pressure is usually set

10 to 15 PSI (.703 – 1.054 kg/cm

2

) above the operating pressure, but

below the maximum pressure of the pressure relief valve. If the pressure

exceeds the high limit pressure control setting, the SteamPac will

automatically shut off.