Specifications and Dimensions

Horizontal SteamPacs

Specifications – Fulton Horizontal SteamPacs from 70 to 350 HP

Models FT

070XH

100XH

150XH

180XH

200XH

250XH

300XH

350XH

Steam Output*

LB/HR

KG/HR

2,415

1,096

3,450

1.565

5,175

2,347

6,210

2,817

6,900

3,130

8,625

3,912

10,350

4,695

12,075

5,477

Input

BTU/HR (1000)

KCAL/HR (1000)

2,343

590

3,347

843

5,021

1,265

6,025

1,518

6,694

1,687

8,368

2,108

10,041

2,530

11,715

2,952

Flow Rate

GPM

M3/HR

160

37

228

52

342

78

411

94

456

104

570

130

684

156

798

182

*From and at 212

o

F (100

o

C). Steam Output is based in a minimum thermal fluid temperature of 425

o

F (218

o

C)

Dimensions – Fulton Horizontal SteamPacs from 70 to 350 HP

Models FT

070XH

100XH

150XH

180XH

200XH

250XH

300XH

350XH

A. Width

IN

MM

68

1,727

80

2,032

80

2,032

80

2,032

96

2,438

96

2,438

96

2,438

96

2,438

B. Length

IN

MM

107

2,718

117

2,972

117

2,972

132

3,353

150

3,810

150

3,810

150

3,810

160

3,810

C. Height

IN

MM

75

1,905

110

2,794

110

2,794

110

2,794

112

2,845

112

2,845

112

2,845

112

2,845

All dimensions are based on 550oF thermal fluid temperature and are subject to change based on

specific customer requirements.