3. Safety Relief Valves

a) When the valves leave the factory, they have been carefully set and tested to ensure that

the seating surfaces are perfect. However, in service, and when the pressure in the

vessel is neat to the set pressure of the valve, the clamping force between the seating

surfaces is very light and any foreign matter lodged between the two surfaces will cause

the valve to leak.

b) Particles lodged on the seating surfaces are, therefore, the first things to look for in the

case of a leaking valve and it is usually sufficient to flush the seating surfaces. If

however, the seating surfaces have been damaged, it will be necessary to replace the

valve.

4. De-scaling

a) The need to de-scale the steam generator is indicated when steam generation becomes

slower and more difficult. Operation of the unit may become erratic.

b) De-scaling is normally carried out chemically by preparing a solution of proprietary

chemical such as “Scale Kleen”, and pouring it into the top of the generator. (Remove the

pressure gauge and use its connection). The pump is run so that the generator is filled. If

possible, some heat is added to warm the solution slightly. Note: It is the responsibility of

the customer to insure that during the descaling of the tube bundle, the tubes are not

chemically attacked and form leaks or cracks.

c) There are two basic ways of ensuring the scale dissolving process continues. Either keep

filling the generator with new solution and drain off the used solution, or use suitable

circulating pump, rubber piping and bucket to continuously circulate the chemical through

the exchanger. Usually the solution changes color, as an indication that the acid is spent.

If necessary, add more solution. Scale cleaning is only completed when no further color

change of new solution takes place. Finally, flush through with an alkali, such as soda

ash (1 oz. Per 250 pounds of nominal steaming rate of the unit) in solution. If desired,

remove the heat exchanger tube bundle and visually inspect the interior.

d) During the cleaning process, the equipment must be vented and no unshielded lights

allowed in the vicinity.

Warning

Follow all safety instructions provided by the manufacturer of the de-scaling

chemical. Read the MSDS sheets that are provided. Disposal of spent solution

must be done in accordance with local regulations.