Section 4 – Maintenance

Warning

Prior to commencement of any work requiring the removal of cover plates at the

opening of the control panel box, the electrical supply to the SteamPac must be

disconnected. The unit should be off and cool before performing work on any

piping or components.

1. Recommended Water Conditions

a) Following are the recommendations for feedwater and boiler water. Contact your local

water treatment professional for testing and treatment recommendations. It is very

important that a strict water management program be maintained.

b) Feedwater

1.

Dissolved Oxygen

less than 0.005 ppm

2.

pH Value

9 to 11 (tested at room temperature)

3.

*Hardness

less than 50 ppm in the form of

CaCO

3

4.

Oil

None

5. Suspended

Solids

None

6.

Organic

Matter

None

7.

Chloride

less than 50 ppm

8.

Total Dissolved Solids

less than 300 ppm

9.

Iron

2

ppm

max.

c) Boiler

Water

1.

Phosphate

30 to 50 ppm in the form of PO

4

2.

Alkalinity

less than 300 ppm in the form of

CaCO

3

3.

Chloride

less than 50 ppm

4.

pH Value

9 to 11 (tested at room temperature)

5.

Total Dissolved Solids

400 – 2,000 ppm

6.

Iron

1

ppm

max.

7.

Silica

180 ppm max. in the form of

SiO

2

8.

Hardness

less than 50 ppm

9. Dissolved

Oxygen

None

10. Suspended Solids

15 ppm

11.

Oil

None

ppm = parts per million; CaCO

3

= Calcium Carbonate; PO

4

= Phosphate; SiO

2

= Silicon Dioxide


*1 Grain Hardness = 17.118 ppm; therefore: 70 ppm = 4.10 grains hardness