Fulton Ancillary Equipment SteamPac Unfired Steam Generators User Manual

Page 9

Advertising
background image

Fulton Thermal Corp.*SteamPac Unfired Steam Generators Manual* Version 2010-0201

Page 9

3. Vent pipe should not be downsized (This may cause pressure build up in the

condensate tank.)

4. Return pipes must not be insulated. This can cause overheating the return system,

causing a vapor lock in the pump.

5. See return system instruction manual for detailed instructions.

Note

Care should be taken to ensure that the blow off receptacle used meets the regulations covering

such vessels. If in doubt consult a Fulton Representative for advice.

Only properly trained personnel should install and maintain water gauge glass and connections.

Wear safety glasses during installation. Before installing, make sure all parts are free of chips and

debris.

Keep gauge glass in original packaging until ready to install. Never operate with lucite gauge

glass guard removed or without brass rods for gauge glass protection kit.

Warning

Improper installation or maintenance of gauge glass and connections can cause immediate or

delayed breakage resulting in bodily injury and/or property damage.

Warning

Under no circumstances should the water softener water flow limit be exceeded.

Note

After installation is complete and prior to operation the pressure vessel should be cleaned.

Note

a) The non-fused disconnect switch on the control panel that controls the feed water pump should

be kept in the “on” position at all times during the boiler operation as well as during the non-

operating period of the boiler.

b) This switch should be turned “off” only when repairs or adjustments should be made.

The pump will continue to operate until the water reaches the correct level in the SteamPac. This

level is approximately the center of the water gauge glass.

Advertising