E-Mon E50-6003200J*-N-KIT User Manual

Page 10

Advertising
background image

GREEN CLASS NET METER

62-0416-01

10

Standard Ranges

4-Wire Wye, 120/208 VAC: 100, 200, 400, 800,1600,3200 Amp

2 Phase, 120/240 VAC: 100, 200, 400, 800,1600,3200 Amp

4-Wire Wye, 277/480 VAC: 100, 200, 400, 800,1600,3200 Amp

3-Wire Delta, 220/240 VAC: 100, 200,400,800,1600,3200 Amp

3-Wire Delta, 480 VAC: 100, 200, 400, 800,1600,3200 Amp

Modem Interface

Cable:

UL-listed Telephone Cord,

6-cond. 300 VAC, Stranded

Cond. 22-26 AWG.

Cable Connector:

RJ-45 male IDC

Input/Output Voltage:

+5 VDC/18 VAC

Ckt Input Isolation

5.3K VAC for 1 Minute

Baud Rate:

9600

IDR Interface Port

Cable:

UL-listed/rated Telephone

Cord. 4-cond.

Input/output Voltage:

Ground-isolated +/-5.4VDC

Cable Connector:

RF-45 Male IDC Or Screw

Terminal Termination

Circuit Input Isolation:

5.3kVAC

Circuit output Isolation:

21.5kVAC

Isolated Pulse/Alarm Outputs

(TB5, TB6):
Output Voltage Potential:

0 VDC to +5 VDC Logic Levels

Mating Plug Connector:

Weidmuller PN: 152876

Signal Isolation Voltage:

5.3K VAC for 1 Minute

Recommended

In-line Fuse

Manufacturer:

Littlefuse

Mfg. Part No:

KLDR.100

Rating:

100mA, Time-delay, 600VAC

Cartridge Fuse

Battery Cell

Description:

Non-rechargeable Cell Used

For Memory Retention

Manufacturer:

Panasonic

Mfg Part No:

CR2032

Working Voltage:

3 VDC

Current Capacity

225 mAHr

Electrolyte:

Manganese Dioxide Lithium

Advertising