6.4.2 Current Sensor Wiring (continued)

If the meter displays an error message (see below), remove the wires from terminals 5

and 6 and install them on terminals 7 and 8 (Phase B). if an error message occurs with

the sensor attached to terminals 7 and 8, try again on terminals 9 and 10 (Phase C).

The “CT Error: * “message will disappear when the current sensor is connected to the

correct terminals (phase).

Error Messages: CT ERROR: A

CT ERROR: A B

CT ERROR: A C

Refer to the section on Current Sensor Diagnostics for assistance in troubleshooting

these errors.

6.4.3 Main Power

After the meter circuit wiring has been examined for correctness, power may be

applied to the circuit board. There are three LEDs located in the upper right corner of

the Meter Board labeled BEAT, STATUS and LOAD. The BEAT and STATUS LEDs will

blink once per second when the meter is operating normally, twice per second if there

is a problem. If the monitored circuit is under load the LOAD LED will actively blink. A

heavy load will cause the LED to blink faster than a light load. Very light loads will

result in an extended blink time.