3 baud rate selection – E-Mon E50-6003200J*-N-KIT User Manual

Page 27

Advertising
background image

GREEN CLASS NET METER

27

62-0416-01

6.9.3 Baud Rate Selection

The communication baud rate is selected by means of a jumper on the circuit board.

There are four (4) selections: 19200 (factory default), 19200, 38400, and 76800.

1. Select 9600 when using the Green Class Net meter with a modem.

2. The baud rate on the meter must always match the baud rate selected in the E-

Mon Energy software; otherwise, communications will not work.

3. After a baud rate change, press CPU Reset to register the change.

4. All meters in the daisy-chain circuit must be set at the same baud rate.

5. The DIP switch is located above the RS-485 terminals.

NOTE: USE ONLY POSITIONS 3 AND 4 - DO NOT CHANGE ANY OTHER

POINTS.

The selections are noted below.

Fig. 13. Baud Rate Selection.

6. Using other than 9600 BAUD will reduce the maximum cable length allowed for

communication.

M33277

3

4

BAUD RATE

ON

ON

9600

OFF ON

19200

ON OFF

38400

OFF OFF

Advertising