GREEN CLASS NET METER

13

62-0416-01

6.0 METER INSTALLATION

6.1 Mounting the Green Class Net Meter

Use appropriately sized mounting hardware to fasten the meter enclosure to the

selected mounting surface.

The four housing mounting holes are centered 6.75” H x 4” W.

NOTE: Units housed in UL Type 1 enclosures must only be installed in indoor envi-

ronments, where they will not be affected by the elements.

6.2 Main Power Board Connections

1. Installing a temporary ground for ESD protection: With all circuits de-energized,

connect a temporary protective earth ground connection for ESD protection.

Prior to performing any unit wiring, be sure to discharge any static on your per-

son.

2. Installing the Green Class Net protective earth ground: Connect an earth ground

wire to the Green Class Net meter’s protective earth ground lug with a torque of

7 N-m. for meters in metal enclosures.

WARNING

Failure to attach the protective earth ground wire securely to the meter creates

a potential shock hazard. Do not operate the meter without a protective earth

ground connection securely installed.

3. Wire Entry: One 3/4” conduit opening is located on the bottom of the unit enclo-

sure. This opening is used for bringing in MAINS power and for current sensor

wiring. Route the appropriate cabling to and through the respective enclosure

opening.

4. After installing the conduit fitting and conduit, verify that each conduit slip nut is

securely tightened to its respective conduit fitting. Any unused openings must be

sealed with a UL rated plugging device suitable for the rating of the enclosure

(check formatting).

NOTE: Metallic enclosure has one additional 1/2” conduit opening at top of unit.

5. Unit MAINS wiring: The first four positions of terminal block TB1, located at the

bottom left corner of the main power board, are clearly labeled Phase A, B, C, N

(neutral). Earth Ground MUST be connected to the PCB mounting screw in the

lower right corner.