5 main power & current sensor wiring diagram, 6 line voltage/current sensor diagnostics, 1 line voltage diagnostics – E-Mon E50-6003200J*-N-KIT User Manual

Page 19: Green class net meter, Ph missing: b c, Fig. 8. current sensor wiring diagram

Advertising
background image

GREEN CLASS NET METER

19

62-0416-01

6.5 Main Power & Current Sensor Wiring Diagram

Fig. 8. Current Sensor Wiring Diagram.

6.6 Line Voltage/Current Sensor Diagnostics

Following is a list of diagnostic messages that may appear on the meter display.

DIAGNOSTIC MESSAGES SHOULD NOT BE ON CONTINUOUSLY WHEN THE

METER IS INSTALLED PROPERLY AND IS IN WORKING ORDER.

6.6.1 Line Voltage Diagnostics

The diagnostics program detects line voltage faults by displaying one of two

messages:

PH Missing: B C or Phase sequence error.

Phase sequence error

indicates that the 3-phase line voltage is not hooked up in the

proper phase sequence. This message should never be seen continuously on the

display during normal operation. The meter will not display correct electrical data in

this condition. The phase sequence problem must be remedied in order for the meter

to work properly.

PH Missing: B C

indicates that the line voltage is missing on Phase B and/or Phase C.

This message will appear whenever the power on either Phase B or Phase C is off.

Screen 5 (Voltage per Phase) will also indicate a loss of line voltage.

∅A ∅B ∅C

∅A

∅B

W B W B W B

N

LINE VOLTAGE

CURRENT SENSORS

∅A

N

∅B

LOAD SOURCE

M33194

3-PHASE INSTALLATION DIAGRAM

NOTES:

LINE VOLTAGE CONNECTIONS: #14-22 AWG

SENSOR CONNECTIONS: W = WHITE LEAD B = BLACK LEAD

NEUTRAL NOT USED IN DELTA SYSTEM.

LITTLEFUSE PART NUMBER KLDR 100.

1/10A 600 VAC INLINE FUSE PER CONDUCTOR. LITTLEFUSE PART

NUMBER KLDR, 100.