3.0 METER TECHNICAL SPECIFICATIONS

Input Voltage

Configuration

3-wire (Delta) Or 4-wire (Wye)

Mains Voltage Input Up To 480 VAC RMS Available
Input Power

6 VA Maximum Rating

Current Sensor

Rating

Up To 3200 Amps RMS AC Available

Power Factor

0.5 Leading Or Lagging

Line Frequency

50-60 Hz

Metering Accuracy

Certified To ANSI C12.20

Voltage Operating

Range

+/-10% Of Rated Load

Temperature Range -20 C To +50 C (Standard indoor enclosure):
Temperature Range -20 C To +70 CNEMA 4X (NEMA 4X outdoor enclosure)
Relative Humidity

Range

0-95% Non-condensing

Altitude

2000 Meters Maximum

Voltage Overload

+25% Continuously: +100% For 20 Cycles

Current Sensor

Overload

100% For 1 Minute Without Damaging Meter

Pollution Degree

Degree 2 In Accordance With IEC 664

Installation

(Overvoltage)

Category

Category 111

Measurement

Category

Category 111

Enclosure Material

Indoor Housing Rating (Standard): NEMA 12

Outdoor Housing Rating (Optional): NEMA 4X

Display Readout

KWh Accumulated,

M33273

EXAMPLE:

E 50 208

400

R

05 KIT

CLASS 5000 METER

INPUT VOLTAGE (208V)

CURRENT RATING (400A)

ENCLOSURE (4X)

EZ7/BACnet IP/NO MODEM

E-MON

SPLIT CORE SENSORS