6.12 Connecting Green Class Net Meters to the USB

Key using RS485

The USB Key plugs into the PC’s USB port and provides a termination point for the

RS485 wiring from the meters. Up to 52 meters can be “Daisy chained” with up to 4000

feet total RS485 wiring. The USB Key is labeled for “plus (+)”, “minus (-)“, and ground

and the wiring must match the same positions on the meters. If more than 52 meters

are to be monitored, additional USB Keys can be utilized to connect them to the PC.

Fig. 15. Connecting Green Class Net Meters to the USB Key using RS485

PC WITH USB

USB KEY

M33425

UP TO 52, GREEN

CLASS NET METERS, ON

RS485 CABLING

UP TO 4000 FEET

TOTAL RS485 CABLE