E-Mon E50-6003200J*-N-KIT User Manual

Page 14

Advertising
background image

GREEN CLASS NET METER

62-0416-01

14

a. Connect the NEUTRAL wire to the appropriate terminal block position.

Fig. 5. Terminal Block TB1.

NOTE: For 3-wire delta-type meters, Do NOT connect the NEUTRAL wire. Remove

the terminal block screw for this position.

b. Earth Ground

Connect the Earth Ground to the PCB mounting screw in the lower right cor-

ner.

c. External Switch Mechanism/In-Line Fuse Installation

To ensure a safe installation, the Green Class Net meter requires an external

switch mechanism, such as a circuit breaker, be installed on the Green Class

Net MAINS input wiring. The switch mechanism must be installed in close

proximity to the meter and easily reachable for the operator. This device

must also be marked as the disconnecting device for the Green Class Net

meter. Install 1/10 Amp Slow Activation in-line fuses with the suitable voltage

rating for each conductor phase at the MAINS input to the meter. The fuses

must be labeled to indicate voltage and current rating as well as element

characteristics. The fuse element must be slow activating type.

d. Connect the three AC main power wires (Phases A, B and C) to their respec-

tive positions as labeled on terminal block TB1 and tighten to 7 in-lb. After all

conductors are connected to each of their respective terminal block positions

and tightened down, verify that each terminal block screw is securely fas-

tened by gently tugging on each conductor.

Verify that no conductor wires are frayed or shorting to adjacent terminal

block positions.

e. Turn ON the AC main power input. The meter display will light up and scroll

through the displays. Each display is visible for 5 seconds. Display screens

are as follows:

Screen 1 - DEL, REC, NET kilowatt-hours (kWh) consumed

Screen 2 - Peak demand (kW) with date & time stamp

Screen 3 - Actual load (kW) with preset date & time

Screen 4 - Average current (amps) per phase

Screen 5 - Average voltage (volts) per phase

Screen 6 - Power factor (PF) per phase

Screen 7 - CO2 COST

Advertising