GREEN CLASS NET METER

25

62-0416-01

6.9 Modem Wiring

Fig. 12. Modem Configuration.

6.9.1 Built-In Modem (RS-232 KEY RM)

The RS-232 key with built-in modem connects the entire RS-485 network of Green

Class Net meters to a telephone line.

Refer to Section 6.7 for RS-485 network connections.

On the back panel of the RS-232 key/modem, the left jack (RS232) is not used in most

cases since there is no local host computer.

The two jacks at the top center of the rear panel on the RS-232 key/modem are for

connecting the phone line. Connect either one of these two jacks to the telephone line.

IMPORTANT:

The telephone line should be dedicated exclusively to the automatic meter

reading system. Never connect to a telephone line used by other modems or

fax machines. If there are telephones connected to this phone line, the propri-

etor must be aware that all phones must be on “hook” in order for the modem

to work. A dedicated phone line is suggested for system reliability.

CHANNEL 2

~~

~~

CHANNEL 3

UP TO 4000

FEET TOTAL

RS-232

KEY RM

RS-232 SERIAL

PORT COM1

THROUGH COM3

MAXIMUM 15 FEET

UP TO 52

GREEN

CLASS NET

METERS PER

CHANNEL

M33424

UP TO 4000

FEET TOTAL

UP TO 52

GREEN

CLASS NET

METERS PER

CHANNEL

CHANNEL 1

AC ADAPTER

PC OR WINDOWS

COMPATIBLE

LOCAL

MODEM

~~

TELEPHONE

LINK