Grounding, Proper grounding is required – Fairbanks MATRIX SCALE HIGHWAY SCALE SYSTEM User Manual

Page 30

Advertising
background image

Section 4: Wiring

11/12

30

51182 Rev. 2

Grounding

Intalogix

Technology systems require one (1) grounding rod per weighbridge, and

one (1) grounding rod per Pit Power Supply.

• These grounding rods are supplied with the scale.
• For accurate operation and protection against damage from lightning strikes, all of

the components of the system must be properly grounded.

Use the following guidelines to correctly ground the system.

• Use 8 AWG or larger wire, or braided ground straps.
• All ground connections should be two feet

(2’), or as short as possible.

• The SSCs and PPSs housing attaches in a clean electrical connection to the

platform frame. The platform frame is then connected to a pit ground rod.

• The insulated WHITE WIRE from the PPS connects directly to the separate

ground rod, and not to the same rod as the weighbridge.

• The 117 VAC SVP Unit connects to a known good ground at the instrument

location.

Use a voltmeter to test the electrical power source available.

The Neutral-to-Ground voltage level must be 0.2 VAC or less.

If unsure, or if the testing reveals higher than 0.2 VAC, install a separate
ground rod at the SVP location, connecting it with braided cable or 8 AWG
wire

C A U T I O N

Proper grounding is REQUIRED

so the Surge Voltage Protection (SVP) adequately shields the

scale from lightning and other electrical interferences!