Control card (refer to figure 19) – Ransburg PulseTrack2 A11515-XXXXX User Manual

Page 39

Advertising
background image

Figure 15: AC Line Filter (Top View)

24VDC Power Supply (refer to Fig-
ures 6, 18, and 19)

1. Turn off AC Power to the control panel at the

Fused Disconnect.

2. Open the cabinet door and pull up on the center

portion of the TB3-F1 and TB3-F2 terminal blocks

to open the AC line fuses.

3. Using a small blade screwdriver, disconnect

the wires from TB1 and TB2 of the 24VDC supply.

4. Using a screwdriver, pull back the retaining

clamp at the bottom of the power supply on the

TB1 side while

at the same time lifting up

on that side of the supply.

5. Remove the power supply from the unit and

replace with a new one, reconnecting the wires

as follows:

Color

From

TB3-Ground

SW1-B3
SW1-A4
SW1-X1

TB4-1C

SW1-X2

TB4-1D

Wire

ID

Green/Yellow

Light Blue

Black

Dark Blue
Dark Blue
Dark Blue
Dark Blue

GND

6
7

24
24

COM
COM

To

TB1-1
TB1-2
TB1-3
TB2-1
TB2-2
TB2-3
TB2-4

6. Push fuse blocks back in, secure cabinet door

and restore AC power.

Control Card (refer to Figure 19)

1. Turn off AC Power to the control panel at the

Fused Disconnect and open the cabinet door.

2. Remove the ribbon cable from the Control Card.

3. Depress the two control card release pins.

4. Pull the Control Card out of its mounting socket

and replace.

5. Install new Control Card in reverse order of

disassembly.

6. Ensure the new Control Card DIP switch SW1

settings are correct (reference Table 6).

7. Secure cabinet door and restore AC power.