Fiber Optic Receiver Module

1. Turn off AC Power to the control panel at the

Fused Disconnect and open the cabinet door.

2. Mark the fiber optic cables for later identification

and remove from the receiver module.

3. Unplug the terminal block(s) from the receiver

module.

4. Using a screwdriver, pry the two tabs on the left

side of the receiver module mounting base loose

from the mounting rail and remove the receiver

module.

5. Snap the new receiver module onto the mount-

ing rail and reinstall the terminal block(s) and fiber

optic cable(s).

6. Secure cabinet door and restore AC power.

Current to Pressure Transducer

(refer to Figure 19) (Steps 3, 4, 5,
and 9 may be skipped if desired)

1. Turn off AC Power to the control panel at the

Fused Disconnect and open the cabinet door.

2. Turn off supply air to the cabinet and bleed off

pressure.

3. Remove the electrical connector from each

transducer assembly.

4. Remove pneumatic tubing from transducer

assembly “IN” and “EXH” ports, as well as from

each transducer output port.

5. Remove the two mounting screws from trans-

ducer mounting manifold and remove assembly

from unit.

6. Remove the two mounting screws from the

suspect transducer and remove transducer from

assembly.

7. Remove the 3 manifold O-rings and replace

with new o-rings supplied with the new transducer.

8. Mount the new transducer using the two mount-

ing screws.

9. Reinstall the manifold assembly in reverse

order of disassembly. Tubing connections should

be made as follows:

10. Secure cabinet door and restore supply air

and AC power.

To

From

EXH

IN

TRD1
TRD2
TRD3
TRD4
TRD5
TRD6

Exhaust Tee

Supply Tee

CL1
CL2
CL3
CL4
CL5
CL6