TROUBLESHOOTING GUIDE (Cont.)

General Problem

Procedure

Solution

Analog Inputs or

Outputs Not Working

Properly

No Connection Fault

(nc) - Temperature/

Humidity Card Only

Temperature / Humid-

ity Probe Not Reading

Properly

1. Improper DIP switch and/

or jumper settings on

Control Card.

2. Defective analog input

source (remote mode).

3. Defective Control Card

1. Loose or defective cable

from control panel to

Temperature/Humidity

Probe

2. Loose internal wiring from

Temperature/Humidity

inputs (TH3-TH7) to

breakout board

1. Improper rotary DIP switch

setting on Temperature/

Humidity Card.

2. Defective temperature/

Humidity probe

1. Correct settings (see Tables 4 and 6).

2. Repair or replace input source.

3. Replace Control Card.

1. Repair or replace cable.

2. Repair wiring.

1. Verify the rotary DIP switch setting (see

Figure 11) is the same as the slot number

of the Temperature/Humidity Card as

indicated by the label inside the cabinet

door.

2. Replace Temperatue/Humidity Probe.