Line fusing, Fuse table – LEESON Chassis Mount Regenerative Control: 175721.00 User Manual

Page 21

Advertising
background image

15

Installation

Line Fusing

Leeson drives require fuses for protection. Use fast acting fuses

rated for 250 VAC or higher, and approximately 150% of the

maximum armature current. Fuse both L1 and L2 when the line

voltage is 230 VAC.

The fuse table below lists the recommended line fuse sizes.

Fuse Table

90 VDC Motor

180 VDC

Max. DC Armature AC Line Fuse

Horsepower

Horsepower

Current (amps)

Size (amps)

1/20

1/10

0.5

3

1/15

1/8

0.8

3

1/8

1/4

1.5

5

1/6

1/3

1.7

5

1/4

1/2

2.5

8

1/3

3/4

3.5

8

1/2

1

5.0

10

3/4

1 1/2

7.5

15

1

2

10

20