Starting and Stopping Methods

26

Twist inhibit wires and separate them from other power-carrying
wires or sources of electrical noise. Use shielded cable if the
inhibit wires are longer than 18 in. (46 cm). If shielded cable is
used, ground only one end of the shield to earth ground. Do
not ground both ends of the shield.

Coast to a stop

To coast the motor to a stop without removing power to the
drive, jumper INHIBIT–RUN terminals 1 and 2 (see Figure 16).
To restart the motor, jumper INHIBIT–RUN terminals 2 and 3. A
single-pole, double-throw switch may be used as a COAST /
RUN switch.

Each drive is assembled with INHIBIT-RUN terminals 2 and
3 jumpered. These terminals must be connected for the
motor to run.

INHIBIT/RUN

TERMINALS

Figure 16. Inhibit-Run Terminals