Line fuse does not blow, but the motor does not run

1. Verify that the speed adjust potentiometer is not

set to its zero speed position.

2. Check the speed adjust potentiometer for

continuity.

3. Verify that the inhibit terminals are not shorted

together.

4. Check that INHIBIT–RUN terminals 2 and 3 are

connected. (See figure 16, page 25)

5. Verify that the drive is receiving AC line voltage.

6. Check that the drive is not in current limit. If the

drive is in current limit, verify that the motor is not

jammed. It may be necessary to increase the

FWD TQ or REV TQ setting if it is set lower than

the current rating of the motor.

7. Check that the speed adjust potentiometer

connections to the terminal block are correct and

not open.