Troubleshooting

44

Line fuse blows

1. Disconnect AC line voltage from the drive.

2. Check that the motor cable and armature are not

shorted or grounded.

a. Armature resistance should measure

approximately 1 to 100 ohms, depending on

motor horsepower.

b. A resistance reading from the motor frame to

either armature side should show open when

an ohmmeter is used on its high resistance

scale.

3. Check that the field circuit is not open.

4. A combination of ambient conditions and frequent

high-current spikes (i.e., reversing) causes fuse to

“nuisance trip”. Consider using a slow-blow fuse or

increasing the fuse rating to 120% of motor

current as stated on the nameplate.