REV 2 Auto‐Ohm 200 S3 / DMOM‐200 S3 / DMOM‐600 USER’S MANUAL

33

 

 

3.4.3. Performing a Quick Test

A quick test can be performed without having to enter the test current, the burn‐in time, and 
the ramp time. For a quick test, a current of 100A is used, and the burn‐in time and ramp time 
are both set to 5 seconds. The Quick Test mode should not be used if the circuit breaker is 
connected to dual grounds (if the unit has the Dual Ground option). 

 

NOTE 

The Quick Test mode should not be used if the circuit breaker is connected to dual 
grounds because the Auto‐Ohm will not monitor the external current probe current. 

Use the steps below to perform a quick test: 

a. Start from the “START‐UP” menu: 

 

Press the 

[3]

 key (QUICK TEST

b. The following screen will be displayed 

 

Press the 

[START]

 key. 

c. The unit will start ramping up the current to 100A. The following screen will be 

displayed: 

 

Once the current has reached 100A, the initial test results will be displayed and the 
burn‐in sequence will be initiated. The following screen will be displayed: 

ramping current

12.30A 27




test in progress...

test parameters

current: 100 amps
burn-in: 5 sec
ramp: 5 sec

"START" TO RUN TEST

1.RUN TEST
2.SETUP
3.QUICK TEST

time: 14:21:34
date: 05/24/11