107

MAPware-7000 Ladder Logic Guide

1010-1041 rev. 00

Instruction 67- ASCII to Hex Conversion

Expression:

Space Requirement: 1 line x 5 column Location Requirement: Middle, Right rail

Function:

When the input is ON, the ASCII characters stored in n registers starting with A is converted into
hexadecimal data and stored in B and after. The lower byte of source A is stored as uppermost
digit of destination B, and followed in this order. The allowable ASCII character in the source
table is “0” (H30) to “9” (H39) and “A” (H41) to “F” (H46). The allowable range of n is 1 to 64.

Execution Condition:

Input

Operation

Output

ERF

OFF

No execution

OFF

---

ON

Normal Execution

ON

---

Conversion Data Error
(no execution)

OFF

Set

Operand:

Coil or Bit

Register

Constant

Index

Name

X

Y B

S

T.

C.

M

X
W

Y
W

B
W

S
W

T C

D

I

J

K

M
W

A

Source

√ √

n

Data Size

1-64

B

Destination

√ √

Example:

When B011 is ON, the ASCII characters stored in 8 words of D0300 to D0307 are converted into
hexadecimal data, and stored in 4 words registers starting with BW040.