Instruction 52- Unsigned

Less Than or Equal To

Expression:

Space Requirement: 1 line x 5 column Location Requirement: Middle, Right rail

Function:

When the input is ON, the data of A and the data of B are compared, and if A is less than or
equal to B, the output is turned ON.

Execution Condition:

Input

Operation

Output

OFF

No execution

OFF

ON

Execution

A < B

ON

A > B

OFF

Operand:

Coil or Bit

Register

Constant

Index

Name

X

Y B

S

T.

C.

M

X
W

Y
W

B
W

S
W

T C

D

I

J

K

M
W

A

Compared

Data

√ √

B

Reference

Data

√ √

Example:

When B0005 is ON, the data of D0125 is compared with the constant data 35000, and if the data
of D0125 is less than or equal to 35000, B020 is turned ON.
If the data of D0125 is 35000, the comparison result is true. Consequently, B020 is turned ON.

If the data of D0125 is 0, the comparison result is false. Consequently, B0020 is turned OFF.

Note

This instruction interprets the data as unsigned integer (0 to 65535).