Maple Systems MAPware-7000 User Manual

Page 156

Advertising
background image

MAPware-7000 Ladder Logic Guide

148

1010-1041 rev. 00

Operand A

Offset

Parameter

Register

Value

A

Present Value

D12

25

A+1

Setpoint Value

D13

100

Operand B

Offset

Parameter

Register

Value

B

Proportional Coefficient

D14

1

B+1

Integral Gain Constant High

D15

4

B+2

Integral Gain Constant Low

D16

10

B+3

Derivative Gain Constant Low

D17

20

B+4

Derivative Gain Constant High

D18

5

B+5

Gap Constant

D19

0

B+6

Limit Constant

D20

100

Operand C

Offset

Parameter

Register

Value

C

Manipulation Value

D21

0

C+1

Last deviation error

D22

78

C+2

Last Present Value

D23

22

C+3

2

nd

to last Present Value

D24

20

C+4

Remainder Value

D25

0

When the normally open contact B4 is ON, the PID1 calculation is performed based upon the
formula given above and the values entered into the registers. The results are stored in the five
consecutive registers as specified by Operand C.