Instruction 20- Multiplexer

Expression:

Space Requirement: 1 line x 6 column Location Requirement: Middle, Right rail

Function:

When the input is ON, the data of the register which is designated by B in the table, size n
starting with A, is transferred to C.

Execution Condition:

Input

Operation

Output

OFF

No execution

OFF

ON

Normal Execution

OFF

Pointer Over (no execution)

ON

Operand:

Coil or Bit

Register

Constant

Index

Name

X Y

B

S

T.

C.

M

X
W

Y
W

B
W

S
W

T C

D

I

J

K

M
W

A

Start of

Table

√ √

n

Table Size

1-64

B

Pointer

√ √

0-63

C

Destination

√ √

Example:

When B010 is ON, the register data which is designated by BW30 is read from the table D0500
to D0509 (10 registers size), and stored in D0005.

If the data of BW30 is 7, D0507 data is transferred to D0005.