Instruction 21- Demultiplexer

Expression:

Space Requirement: 1 line x 6 column Location Requirement: Middle, Right rail

Function:

When the input is ON, the data of A is transferred to the register which is designated by B in the
table, size n starting with C.

Execution Condition:

Input

Operation

Output

OFF

No execution

OFF

ON

Normal Execution

OFF

Pointer Over (no execution)

ON

Operand:

Coil or Bit

Register

Constant

Index

Name

X Y

B

S

T.

C.

M

X
W

Y
W

B
W

S
W

T C

D

I

J

K

M
W

A

Source

√ √

n

Table Size

1-64

B

Pointer

√ √

0-63

C

Start of

Table

√ √

Example:

When B011 is ON, the data of XW04 is transferred to the register which is designated by BW30
in the table D0500 to D0509 (10 registers size).

If the data of BW30 is 8, XW04 data is transferred to D0508.