Instruction 17- table block transfer – Maple Systems MAPware-7000 User Manual

Page 39

Advertising
background image

31

MAPware-7000 Ladder Logic Guide

1010-1041 rev. 00

Instruction 17- Table Block Transfer

Expression:

Space Requirement: 1 line x 5 column Location Requirement: Middle, Right rail

Function:

When the input is ON, the data of n registers starting with A are transferred to n registers
starting with B in a block. The allowable range of the table size n is 1 to 1024 words.

Execution Condition:

Input

Operation

Output

OFF

No execution

OFF

ON

Execution

ON

Operand:

Coil or Bit

Register

Constant

Index

Name

X Y

B

S

T.

C.

M

X
W

Y
W

B
W

S
W

T C

D

I

J

K

M
W

A

Start of

Source

n

Table Size

1-1024

B

Start of

Destination

√ √

Example:

When B010 is ON, the data of D0500 to D0509 (10 registers) are block transferred to D1000 to
D1009, and the output is turned ON.

Note: The source and destination tables can overlap.