Instruction 96- upper limit – Maple Systems MAPware-7000 User Manual

Page 163

Advertising
background image

155

MAPware-7000 Ladder Logic Guide

1010-1041 rev. 00

Instruction 96- Upper Limit

Expression:

Space Requirement: 1 line x 6 column Location Requirement: Middle, Right rail

Function:

When the input is ON, this function compares the value in A with the Upper Limit value as set in
B. If the upper limit value is not exceeded, then value in A is placed into C. If upper limit is
exceeded, the upper limit value is placed into C:

If A < B, then C = A.

If A > B, then C = B.

Execution Condition:

Input

Operation

Output

OFF

No execution

OFF

ON

Execution: not limited (A<B)

OFF

Execution: limited (A>B)

ON

Operand:

Coil or Bit

Register

Constant

Index

Name

X

Y B

S

T.

C.

M

X
W

Y
W

B
W

S
W

T C

D

I

J

K

M
W

A

Operation

Data

√ √

B

Upper Limit

√ √

C

Destination

√ √

Example:

When B030 is ON, the upper limit operation is executed for the data of BW018 by the data of
D1200, and the result is stored in BW021.

Advertising