3. Next, press the [ENTER] key to display the following message:
OIT Model
Message
OIT3100 and OIT4100 Series
Password?
All other models
Enter Setup Password?
4. Type the setup password and then press the [ENTER] key on the OIT. If there is no
setup pasword, just press the [ENTER] key. The following message appears:
OIT Model
Message
OIT3100 and OIT4100 Series
Down/Upload Mode? Y
All other models
Download/Upload computer? YES
5. Press the [ENTER] key to display the message:
OIT Model
Message
OIT3100 and OIT4100 Series
Ready for Transfer to/from STEPware!
All other models
Ready for Transfer to/from STEPware!
Computer will reset OIT when done...
The OIT is now in download/upload mode waiting for instructions from the
STEPware-100 configuration software.
If You Have Trouble Entering Configuration Mode
1. If the Initializing message is followed by Terminal Now Ready!, the OIT did not
enter Configuration mode and you need to repeat step 1.
2. If the OIT Brightness, Disp View Angle, or Baud Rate message displays instead of
Parameters?, Local Setup Access has been disabled. You will need to enable Local
Setup Access by connecting the OIT to a host controller and having the host
controller send the Keyboard Control control command to the OIT. Refer to
Appendix A: Control Commands for more information. Please refer to Appendix F:
Troubleshooting for more tips on entering configuration mode.
3. If the OIT’s display remains blank and you hear a steady beeping, the OIT does not
contain a complete project and is waiting in download mode for STEPware-100 to
download a project. Since the OIT is already in download mode, you should proceed
to the next step, Transfer Project.
Transfer Project
When you receive your OIT from the factory, it does not contain any information on how
it is to operate. Therefore, the first time you download a project to the OIT you must also
download the Operational Software. Downloading the Operational Software takes
approximately three minutes to complete. Sending only the project file reduces the
download time to approximately 30 seconds.
Getting Started
11
1010-0096, Rev. 04