3-Wire RS-422/485 (Network mode)

If you decide to use 3-wire RS-422/485, the following limitations apply:
1. The host controller must disable or tri-state its RS-485 transmitter when it is not

sending data to the OITs on the network. To simplify programming, the host should

disable or tri-state its RS-485 receiver whenever transmitting.

2. The ability to stay logged on to a particular OIT by sending the command terminator

instead of the line terminator is not available in this mode. Therefore, each command

sent from the host controller should end with the appropriate line terminator.

3. If the host controller sends a command that requires a response from the OIT, the host

controller must wait for a response from the OIT before sending another command.

Otherwise, a situation can occur in which the OIT and the host controller attempt to

transmit at the same time causing unpredictable results.

4. The ASCII strings sent by the OIT’s function keys should not include any control

characters which the other OITs on the network could misinterpret, such as the line

terminator or command terminator.

Network Termination

The com-link cable must be properly terminated to reduce the amount of interference and

noise pickup from the surrounding environment. This is accomplished by using a

termination circuit at both ends of the network cable. The following figure shows a

typical termination circuit. The host termination is only needed if the host controller’s

RS-422/485 adapter does not contain any built-in terminator circuitry. The end

termination must be done at the extreme end of the com-link cable.

Getting Started

19

1010-0096, Rev. 04

5

RXD+

Return

4

DE9P

RXD- 1

9

TXD-

TXD+

6

Shield

OIT

From or To

Host or OIT

CHASSIS GND

RXD+/TXD+

RXD-/TXD-

SIG GND
SIG GND

5

COM
RXD+
RXD-

+24V

3
4

2

1

TB1

Shield

OIT

From or To

Host or OIT

+24V
GND

Power Supply

RTN

8

*

*

RTN and COM are internally connected in OIT.

*

7

TXD+
TXD-

6

CHASSIS GND
RXD+/TXD+
RXD-/TXD-

SIG GND
SIG GND

Shield

OIT

From or To

Host or OIT

CHASSIS GND

RXD+/TXD+

RXD-/TXD-

SIG GND
SIG GND

4

RXD+

Return

8

TXD+ 1

7

TXD-

RXD-

2

RJ45

3-wire RS422/485 (OIT3100 and OIT4100 Series, except OIT3160/4160)