A3-7 – Yokogawa EJX930A User Manual

Page 102

Advertising
background image

<Appendix 3. Input Selector (IS) Block>

A3-7

IM 01C25T02-01E

When SELECT TYPE is “Minimum”
The IS block selects the input with the minimum value among valid inputs and transmits the value of that input

to OUT. The number of the selected input is transmitted to SELECTED.

IN_1 = 23

SELECT_TYPE = Minimum

STATUS_OPTS

MIN_GOOD = 1

SELECTION

SELECTED = 4

OUT = 2.34

IN_2 = 34.5

IN_3 = 45

IN_4 = 2.34

IN_5 = 23.6

IN_6 = 15.5

IN_7 = 32.5

IN_8 = 27.4

DISABLE_1 = OFF

DISABLE_2 = OFF

DISABLE_3 = OFF

DISABLE_4 = OFF

DISABLE_5 = OFF

DISABLE_6 = OFF

DISABLE_7 = OFF

DISABLE_8 = OFF

OP_SELECT = 0

FA0305.ai

Figure A3.5 Example (4)

Advertising