<Appendix 4. Arithmetic (AR) Block>

A4-7

IM 01C25T02-01E

Relative

Index

Parameter

Write

Mode

Valid

Range

Initial

Value

View

Description / Remarks

1 2 3 4

21

BIAS_IN_1

0

4 IN_1 bias

22

GAIN_IN_1

0

4 IN_1 gain

23

BIAS_IN_2

0

4 IN_2 bias

24

GAIN_IN_2

0

4 IN_2 gain

25

BIAS_IN_3

0

4 IN_3 bias

26

GAIN_IN_3

0

4 IN_3 gain

27

COMP_HI_

LIM

+INF

4 High limit of compensation factor f.

28

COMP_LO_

LIM

-INF

4 Low limit of compensation factor f.

29

ARITH_

TYPE

1 to 10

0x01

1 Computation algorithm identification no.

Value

Selection Name

Description

1

Flow compensation, linear

Flow compensation (linear)

2

Flow compensation, square

root

Flow compensation (square

root)

3

Flow compensation,

approximate

Flow compensation

(approximate expression)

4

BTU flow (*)

Quantity of heat calculation

5

Traditional Multiply Divide

Multiplication and division

6

Average

Average calculation

7

Traditional summer

Summation

8

Fourth order Polynomial,

Type 1

4th-order (auxiliary input)

polynomial computation

9

HTG level compensation (*) HTG-level compensation

10

Fourth order Polynomial,

Type 2

4th-order (main input)

polynomial computation

* BTU stands for British thermal unit.

HTG stands for

hydrostatic tank gauging.

30

BAL_TIME

More

than 0

0

4 Time taken to return to the set value.

31

BIAS

0

4 Bias value used to calculate the output.

32

GAIN

1

4 Gain value used to calculate the output.

33

OUT_HI_

LIM

+INF

4 Maximum output value.

34

OUT_LO_

LIM

-INF

4 Minimum output value.

35

UPDATE_

EVT

Indicates event information if an update event (setting change)

occurs.

36

BLOCK_

ALM

Indicates alarm information if a block alarm occurs.