<Appendix 8. Advanced Diagnostics>

A8-15

IM 01C25T02-01E

Relative

Index Index

Parameter Name

Factory

Default

Write

Mode

Explanation

73

2073 REF_LIM_FDPMIN

7.0E-10

AUTO Lower limit to judge whether

REFERENCE_FDP is available for

ILBD operation. Writable only when Diag Mode is Stop(0).

74

2074 REF_LIM_FSPMIN

1.0E-10

AUTO Lower limit to judge whether

REFERENCE_FSPL and

REFERENCE_FSPH are available for ILBD operation.

Writable only when Diag Mode is Stop(0).

75

2075 REF_LIM_BLKFMAX 0.5

AUTO Upper limit to judge whether

REFERENCE_BLKF is available for

ILBD operation.

Writable only when Diag Mode is Stop(0).

76

2076 COMP_FLAG

0

(Compensation)

AUTO Whether RATIO_FDP is referred by CRATIO_FDP or NRATIO_FDP

is selected.

• Compensation(0)

• Non-Compensation(1)

77

2077 DIAG_LIM

Refer to

Table A8.2

AUTO Set the ten threshold values for ILBD.

[1] Upper limit to detect “A Blocking”

[2] Lower limit to detect “B Blocking”

[3] Upper limit to detect “Large Fluctuation of Low Side”

[4] Lower limit to detect “Low Side Blocking”

[5] Upper limit to detect “Large Fluctuation of High Side”

[6] Lower limit to detect “High Side Blocking”

[7] Upper limit to detect “High Side Blocking” by using VALUE_

BLKF

[8] Lower limit to detect “Low Side Blocking” by using VALUE_BLKF

[9] Upper limit to detect “Outside Diagnosis Range”

[10] Lower limit to detect “Outside Diagnosis Range”

Writable only when DIAG_MODE is Stop(0).

78

2078 DIAG_COUNT

3

AUTO When the statistical value such as VALUE_FDP and VALUE_BLKF

exceeds consecutively the threshold by number of times preset to

this parameter, it is estimated that the impulse line is plugged.

Writable only when DIAG_MODE is Stop(0).

If the process fluctuation values are unsteady, increase this

numbers to enhance the accuracy of the blockage detection.

79

2079 REFERENCE_TIME 0x00000000

AUTO The date and time when the reference values were obtained are

automatically recorded when DIAG_MODE is set to Reference (2).

80

2080 REFERENCE_FDP

0x00, 0

AUTO The reference value of VALUE_FDP obtained at normal operating

condition is automatically recorded when DIAG_MODE is set to

Reference (2).

81

2081 REFERENCE_FSPL 0x00, 0

AUTO The reference value of VALUE_FSPL obtained at normal operating

condition is automatically recorded when DIAG_MODE is set to

Reference (2).

82

2082 REFERENCE_FSPH 0x00, 0

AUTO The reference value of VALUE_FSPH obtained at normal operating

condition is automatically recorded when DIAG_MODE is set to

Reference (2).

83

2083 REFERENCE_BLKF 0x00, 0

AUTO VALUE_BLKF obtained under normal condition.

84

2084 REFERENCE_

DPAVG

0x00, 0

AUTO The average value of differential pressure obtained at normal

operating condition is automatically recorded when DIAG_MODE is

set to Reference (2).

85

2085 VALUE_TIME

The date and time when the statistical values such as VALUE_FDP

and VALUE_BLKF were calculated are recorded.

86

2086 VALUE_FDP

Average value of the sum of squares of differential pressure/

pressure fluctuations.

87

2087 VALUE_FSPL

Average value of the sum of squares of low-pressure side static

pressure fluctuations.

88

2088 VALUE_FSPH

The average value of the sum of squares of low-pressure side static

pressure fluctuations.

89

2089 VALUE_BLKF

Blockage degree characterized in comparison of high-pressure side

and low-pressure side pressure fluctuation values.

90

2090 VALUE_DPAVG

Ratio of the average of differential pressure/pressure to the

maximum span of an EJX

91

2091 RATIO_FDP

CRATIO_FDP or NRATIO_FDP is used by COMP_FLG setting.

VALUE_FDP decreases and this parameter is used to determine

whether single or both side is plugged.