<Appendix 8. Advanced Diagnostics>

A8-9

IM 01C25T02-01E

Bit

Alarm status

D

IA

G

_H

_

A

LM

D

IA

G

_L

_

A

LM

FL

G

_

TE

M

P_

A

LM

5 Low Side Blocking

6 High Side Blocking

7 B Blocking

8 Invalid Ref BlkF

9 Invalid Ref fSPh

10 Invalid Ref fSPl

11 Invalid Ref fDP

12 Outside Diagnosis Range

13 Flg Temp Low Alarm

14 Flg Temp High Alarm

15 Reflect Blockage to PV/SV/TV

status

Note: The bit 13 and 14 are used for Heat trace monitorig

function.

Outside Diagnosis Range

1) dpavgmax

The dpavgmax, DIAG_LIM [9], is the upper

limit of the diagnostic capability range. The limit

value can be changed when DIAG_MODE is

“Stop”.

VALUE_DPAVG indicates the ratio of the

average of differential pressure to the maximum

span regarded as 1. When VALUE_DPAVG

exceeds this limit, “Outside Diagnosis Range”

is generated so that the blockage detection

becomes impossible.

2) dpavgmin

The dpavgmin, DIAG_LIM [10], is the lower

limit of the diagnostic capability range. The limit

value can be changed when DIAG_MODE is

“Stop”.

When VALUE_DPAVG is below this limit,

“Outside Diagnosis Range” is generated so that

the blockage detection becomes impossible.

<Example>
When the level range that can be measured by the

transmitter with 100 kPa span is -80 to 80 kPa, the

limits are set as follows.

• dpavgmax: 0.80

• dpavgmin: -0.80

1.000

0.000

0.80

-0.80

-1.000

Detectable

range

DPAvg

FA0807.ai

Outside Diagnosis Range

Outside Diagnosis Range

Invalid Ref BlkF, fSPh, fSPl, or fDP

This alarm indicates that the reference value under

normal condition is invalid. If REFERENCE_BLKF

is invalid, the blockage detection excluding VALUE_

BLKF is carried out. If blockage detection function

based on VALUE_BLKF is required, obtain the

reference value again.
Also when REFERENCE_DPAVG is below DIAG_

LIM [10] or exceeds DIAG_LIM [9], all reference

value becomes invalid so that “Invalid Ref fDP”,

“Invalid Ref fSPl”, “Invalid Ref fSPh”, and “Invalid

Ref BlkF” are generated.

A8.2.5.4 Alarm Masking

DIAG_OPTION

The alarms linked to an analog alert and LCD

display are selected by DIAG_OPTION in the

SENSOR Transducer block. The BIT of DIAG_

OPTION is corresponding to that of DIAG_ERR.
To link the alarm to an analog alert and LCD display,

follow the procedure below.

1) Set "Stop" to DIAG_MODE.

2) Check each checkbox of the alarm, which is

selectable from bit 2 to bit 14.

Note: The bit 13 and 14 are used for Heat trace monitoring

function.

Set to “Calculation” after setting the parameters.