<9. Parameter Lists>

9-7

IM 01C25T02-01E

Relative

Index Index

Parameter Name

Factory Default Write

Mode

Explanation

54

2054

CAP_GASKET_MTL

Depend on

Specify

O/S

Material of capsule gasket

55

2055

FLANGE_MTL

Depend on

Specify

O/S

Material of flange

56

2056

D_VENT_PLUG

Depend on

Specify

O/S

Material of drain or vent plug

57

2057

FLANGE_TYPE

Depend on

Specify

O/S

Flange type

58

2058

REM_SEAL_

ISOL_MTL

Depend on

Specify

O/S

Material of isolating diaphragms for remote seal

59

2059

FLANGE_SIZE

Depend on

Specify

O/S

Flange size

60

2060

REM_SEAL_ NUM

Depend on

Specify

O/S

Number of remote seal

61

2061

REM_SEAL_

FILL_FLUID

Depend on

Specify

O/S

Types of fill fluid in remote seals.

62

2062

REM_SEAL_ TYPE

Depend on

Specify

O/S

Types of remote seals

63

2063

ALARM_SUM

Alarm Disable

The current alert status, unacknowledged states, unreported

states, and disabled states of the alarms associated with the

function block.

64

2064

AUTO_RECOVERY

1 (ON)

O/S

Permission of auto recovery from sensor errors

65

2065

MS_CODE

Null

Model suffix and codes

66

2066

DIAG_MODE

Stop (0)

Used for ILBD. Refer to A8.2.12.

67

2067

DIAG_PERIOD

180 (s)

Used for ILBD. Refer to A8.2.12.

68

2068

DIAG_PRI

1

Used for ILBD. Refer to A8.2.12.

69

2069

DIAG_ERR

0x0000

Used for ILBD. Refer to A8.2.12.

70

2070

DIAG_H_ALM

Used for ILBD. Refer to A8.2.12.

71

2071

DIAG_L_ALM

Used for ILBD. Refer to A8.2.12.

72

2072

DIAG_OPTION

0x08FC

Used for ILBD. Refer to A8.2.12.

73

2073

REF_LIM_FDPMIN

7E-10

Used for ILBD. Refer to A8.2.12.

74

2074

REF_LIM_FSPMIN

1E-10

Used for ILBD. Refer to A8.2.12.

75

2075

REF_LIM_BLKFMAX

0.5

Used for ILBD. Refer to A8.2.12.

76

2076

COMP_FLAG

0

Used for ILBD. Refer to A8.2.12.

77

2077

DIAG_LIM

Refer to Table

A8.2

Used for ILBD. Refer to A8.2.12.

78

2078

DIAG_COUNT

3, 3, 3, 3, 3

Used for ILBD. Refer to A8.2.12.

79

2079

REFERENCE_TIME

0x00000000

Used for ILBD. Refer to A8.2.12.

80

2080

REFERENCE_FDP

0x00, 0

Used for ILBD. Refer to A8.2.12.

81

2081

REFERENCE_FSPL

0x00, 0

Used for ILBD. Refer to A8.2.12.

82

2082

REFERENCE_FSPH

0x00, 0

Used for ILBD. Refer to A8.2.12.

83

2083

REFERENCE_BLKF

0x00, 0

Used for ILBD. Refer to A8.2.12.

84

2084

REFERENCE_DPAVG 0x00, 0

Used for ILBD. Refer to A8.2.12.

85

2085

VALUE_TIME

Used for ILBD. Refer to A8.2.12.

86

2086

VALUE_FDP

Used for ILBD. Refer to A8.2.12.

87

2087

VALUE_FSPL

Used for ILBD. Refer to A8.2.12.

88

2088

VALUE_FSPH

Used for ILBD. Refer to A8.2.12.

89

2089

VALUE_BLKF

Used for ILBD. Refer to A8.2.12.

90

2090

VALUE_DPAVG

Used for ILBD. Refer to A8.2.12.

91

2091

RATIO_FDP

Used for ILBD. Refer to A8.2.12.

92

2092

RATIO_FSPL

Used for ILBD. Refer to A8.2.12.

93

2093

RATIO_FSPH

Used for ILBD. Refer to A8.2.12.

94

2094

CRATIO_FDP

Used for ILBD. Refer to A8.2.12.

95

2095

NRATIO_FDP

Used for ILBD. Refer to A8.2.12.

96

2096

DIAG_APPLICABLE

Used for ILBD. Refer to A8.2.12.

97

2097

FLG_TEMP_VAL

0

Used for Heat trace monitoring. Refer to A8.3.6.

98

2098

FLG_TEMP_RANGE

-50.0 to 130.0°C

Used for Heat trace monitoring. Refer to A8.3.6.

99

2099

FLG_TEMP_COEF

0

Used for Heat trace monitoring. Refer to A8.3.6.

100

2100

FLG_TEMP_PRI

1

Used for Heat trace monitoring. Refer to A8.3.6.

101

2101

FLG_TEMP_H_LIM

130

Used for Heat trace monitoring. Refer to A8.3.6.