<9. Parameter Lists>

9-10

IM 01C25T02-01E

Relative

Index

Index

AI1

Index

AI2

Index

AI3 Parameter Name Factory Default

Write

Mode

Explanation

3

4003

4103

4203

STRATEGY

1

AUTO The strategy field can be used to identify grouping

of blocks. This data is not checked or processed

by the block.

4

4004

4104

4204

ALERT_KEY

1

AUTO The identification number of the plant unit. This

information may be used in the host for sorting

alarms, etc.

5

4005

4105

4205

MODE_BLK

AUTO

AUTO The actual, target, permitted, and normal modes

of the block.

6

4006

4106

4206

BLOCK_ERR

This parameter reflects the error status

associated with the hardware or software

components associated with a block. It is a bit

string, so that multiple errors may be shown.

7

4007

4107

4207

PV

Either the primary analog value for use in

executing the function, or a process value

associated with it. May also be calculated from

the READBACK value of an AO block.

8

4008

4108

4208

OUT

Value =

MAN

The primary analog value calculated as a result of

executing the function.

9

4009

4109

4209

SIMULATE

Disable

AUTO Allows the transducer analog input or output to

the block to be manually supplied when simulate

is enabled. When simulation is disabled, the

simulate value and status track the actual value

and status.

10

4010

4110

4210

XD_SCALE

Specified at the

time of order

O/S

The high and low scale values, engineering units

code, and number of digits to the right of the

decimal point used with the value obtained from

the transducer for a specified channel.

11

4011

4111

4211

OUT_ SCALE

Specified at the

time of order

O/S

The high and low scale values, engineering units

code, and number of digits to the right of the

decimal point to be used in displaying the OUT

parameter and parameters which have the same

scaling as OUT.

12

4012

4112

4212

GRANT_DENY

0

AUTO Options for controlling access of host computers

and local control panels to operating, tuning and

alarm parameters of the block.

13

4013

4113

4213

IO_OPTS

0

O/S

Options which the user may select to alter input

and output block processing

14

4014

4114

4214

STATUS_OPTS

0

O/S

Options which the user may select in the block

processing of status

15

4015

4115

4215

CHANNEL

AI1: 1

AI2: 2

AI3: 4

O/S

The number of the logical hardware channel that

is connected to this I/O block. This information

defines the transducer to be used going to or from

the physical world.

1:PV

2:SV

3:TV

4:CAP_TEMP_VAL

5:AMP_TEMP_VAL

6:FLG_TEMP_VAL

16

4016

4116

4216

L_TYPE

Specified at the

time of order

MAN

Determines if the values passed by the

transducer block to the AI block may be used

directly (Direct) or if the value is in different units

and must be converted linearly (Indirect), or with

square root (Ind Sqr Root), using the input range

defined by the transducer and the associated

output range.

17

4017

4117

4217

LOW_CUT

Linear: 0%

Square root: 10%

of OUT_SCALE

AUTO Limit used in square root processing. A value of

zero percent of scale is used in block processing

if the transducer value falls below this limit. This

feature may be used to eliminate noise near zero

for a flow sensor. The setting is in an engineering

unit of OUT_SCALE.

18

4018

4118

4218

PV_FTIME

0 (s)

AUTO Time constant of a single exponential filter for the

PV, in seconds.

19

4019

4119

4219

FIELD_VAL

Raw value of the field device in percent of thePV

range, with a status reflecting the Transducer

condition, before signal characterization (L_

TYPE) or filtering (PV_FTIME).