Yokogawa EJX930A User Manual

Page 18

Advertising
background image

<2. Handling Cautions>

2-7

IM 01C25T02-01E

Note 3. Installation should be in accordance with

Canadian Electrical Code Part I and local

Electrical Code.

Note 4. Do not alter drawing without authorization

from CSA.

Electrical Data:

• Rating 1 (Entity)

For Groups A, B, C, D, E, F, and G or Group IIC

Ui (vmax) = 24 V dc

Ii (Imax) = 250 mA

Pi (Pmax) = 1.2 W

Ci = 3.52 nF

Li = 0 μH

or

• Rating 2 (FISCO)

For Groups A, B, C, D, E, F, and G or Group IIC

Ui (vmax) = 17.5 V dc

Ii (Imax) = 380 mA

Pi (Pmax) = 5.32 W

Ci = 3.52 nF

Li = 0 μH

or

• Rating 3 (FISCO)

For Groups C, D, E, F, and G or Group IIB

Ui (vmax) = 17.5 V dc

Ii (Imax) = 460 mA

Pi (Pmax) = 5.32 W

Ci = 3.52 nF

Li = 0 μH

Installation requirements;

Po ≤ Pi Uo ≤ Ui Io ≤ Ii,

Co ≥ Ci + Ccable Lo ≥ Li + Lcable

Vmax ≥ Voc Imax ≥ Isc

Ca ≥ Ci + Ccable La ≥ Li + Lcable

Uo, Io, Po, Co, Lo,Voc, Isc, Ca and La are

parameters of barrier.

Caution for CSA Non-incendive type.

(Following contents refer to “DOC. No.

ICS018)

Installation Diagram for Non-incendive

or Type of protection "n" (Division 2

Installation)

Non-Hazardous location

Hazardous location

F0206.ai

Terminator

CSA Certified

Equipment [nL]

Pressure

Transmitter

SUPPLY

Terminator

+

Transmitter

+

Transmitter

+

+

+

Note 1. Installation should be in accordance with

Canadian Electrical Code Part I and local

Electrical Code.

Note 2. Dust-tight conduit seal must be used when

installed in class II and III environments.

Note 3. Do not alter drawing without authorization

from CSA.

Electrical Data:

• Rating (including FNICO)

Ui or Vmax = 32 V

Ci = 3.52 nF

Li = 0 μH