<Appendix 3. Input Selector (IS) Block>

A3-15

IM 01C25T02-01E

Relative

Index

Parameter

Write

Mode

Valid Range

Initial

Value

View

Description / Remarks

1 2 3 4

20

MIN_GOOD

0-8

0

1 Parameter specifying the minimum required number

of inputs with “good” status If the number of inputs with

“good” status is less than the value of MIN_GOOD, input

selection is canceled.

21

SELECTED

0-8

0

2

2

Indicates the number of the selected input. However,

it indicates the number of inputs used to calculate the

average if SELECT_TYPE = Average.

If no input is selectable or if there are multiple inputs, it

becomes “0” (none).

22

OP_

SELECT

0-8

0

2

2

A parameter to forcibly employ the input of a selected

number (Operator-settable).

23

UPDATE_

EVT

-----

-----

Indicates event information if an update event (setting

change) occurs.

24

BLOCK_

ALM

-----

-----

Indicates alarm information if a block alarm occurs.

25

IN_5

0

5

5

Input 5

26

IN_6

0

5

5

Input 6

27

IN_7

0

5

5

Input 7

28

IN_8

0

5

5

Input 8

29

DISABLE_5

0, 1

0

2

2

Selector switch to disable input 5 from being selected.

30

DISABLE_6

0, 1

0

2

2

Selector switch to disable input 6 from being selected.

31

DISABLE_7

0, 1

0

2

2

Selector switch to disable input 7 from being selected.

32

DISABLE_8

0, 1

0

2

2

Selector switch to disable input 8 from being selected.